What is Floating Neutral ? Easiest Explanation with Circuit Simulation - YouTube

Channel: Gaurav J - TheElectricalGuy

[0]
In this video, you’ll understand the concept of Floating neutral, what are it’s effect
[5]
and what causes floating neutral.
[7]
I’ll also show you a live circuit simulation of floating neutral, which will make things
[13]
crystal clear.
[14]
So, to understand the concept of floating neutral, you need to watch the video.
[21]
We know that, when the load on the system is balanced, sum of return currents of all
[31]
the three phases is zero.
[34]
And hence, current flowing through neutral conductor is also zero at every instance.
[39]
This we have learned in detail in the video in which I explained, “if we can remove
[43]
the neutral wire”.
[45]
If you have’t watched it, I’ll give link for that video down in the description of
[48]
this video.
[49]
Go check that out.
[50]
It’ll help you to understand this video more clearly.
[53]
To understand the floating neutral, you must know why neutral is necessary.
[57]
That’s why we’ll look at that first.
[59]
So, when the load is balanced, current flowing through neutral is zero.
[64]
And in that case, we can even remove the neutral wire.
[67]
But this situation is not practical is distribution system.
[71]
In distribution system, the load is always unbalanced.
[75]
And that’s when neutral comes into picture.
[77]
Now, when I am saying balanced load that means, all the load connected are taking equal amount
[83]
of power.
[85]
And when load connected takes different amount of powers then the load is said to be unbalanced.
[89]
Remeber that.
[90]
Now, let’s go to our distribution transformer.
[94]
This is connected in delta-star manner meaning, primary or incoming is connected in delta
[99]
connection and secondary or outgoing is connected in Star connection.
[104]
This common point right here, is our neutral point.
[109]
This here is our load.
[110]
Which are three different houses.
[112]
Of course, power consumption of these load will be different.
[115]
When the load in not balanced or equal on all the phases, sum of return currents will
[121]
not be zero.
[122]
This I’ll also show you in a simulation in few minutes.
[125]
So this is where we’ll need neutral wire.
[128]
Job of Neutral wire is to carry the unbalanced current and help in keeping the phase to neutral
[134]
& phase to phase voltage constant.
[137]
Which is our case, let’s say, phase to neutral is 250 volts & phase to phase is 433V.
[144]
These voltage you’ll get even if the load is unbalanced when neutral is there.
[149]
I’ll tell you what I am trying to say here via a circuit simulation.
[154]
Here we have our three phase supply connected in star.
[157]
That’s our neutral point connected to ground.
[160]
We also have a three LEDs connected to each phase in star as load.
[165]
Each LED is consuming 5 watts.
[169]
….
[170]
So, we can say the load is balanced.
[173]
We have also connected neutral wire here.
[176]
Now, across each load we have connected a voltmeter to check the voltage across each
[182]
load.
[185]
And an ammeter is connected in series in the neutral wire.
[187]
This ammeter will tell us if any current flows through neutral.
[191]
Now, let’s start the simulation.
[195]
In the first scenario the load is balanced.
[197]
And as you can see, no current is flowing through neutral wire.
[202]
You can see ammeter read 0 A. Which proves our statement.
[207]
In this case even if we remove the neutral wire it will not affect the circuit.
[215]
……. as you can see, even when the neutral is removed voltage across each load is constant
[221]
that is 250 V. Let’s connect the neutral back.
[226]
Now, in scenario two, we’ll unbalance the load.
[228]
Let me make the second LED 10 watts and the third one 3 watts.
[238]
All LED now taking different power, which means the load is unbalanced.
[244]
Now let’s start the simulation.
[246]
As you can see the ammeter is now reading 32.2 mA.
[252]
This is the current coming because of the unbalanced load.
[255]
Which proves our second statement also.
[259]
Even if the load is unbalanced, voltage across each load is constant I.e. 250V.
[265]
You can see the reading of voltmeter.
[268]
That’s why neutral wire is of so much importance in distribution system.
[275]
Now, let’s say the neutral wire is broken somewhere.
[280]
Since the neutral is broken, current will try to find out another way to return.
[284]
This will create unequal voltage across the loads.
[288]
Some load may have very high voltage than normal and some may have very less voltage
[292]
than normal.
[293]
And in this case, the phase to neutral and phase to phase voltage keeps on changing as
[299]
the load varies.
[301]
And hence, this situation is called as “Floating Neutral” or some people also calls it as
[307]
floating ground.
[309]
Floating neutral does’t mean that the neutral wire floats in air.
[312]
As the value of potential of such open neutral keeps on changing or it keeps on floating
[318]
based on the load, it is called as “Floating Neutral” or “Floating ground”.
[323]
I’ll also show you the floating neutral in our simulation in few minutes.
[328]
And that’s very interesting.
[330]
And by the way, if you are new on this channel & interested in learning electrical engineering
[333]
in easiest way, then do subscribe to my channel.
[342]
Floating neutral can be very dangerous.
[344]
It causes, very high or very low voltage across the load.
[348]
Load connected phase to neutral can experience maximum voltage of phase to phase.
[353]
Which in our case is 433 volts.
[356]
So, if you see here, our appliance or any device which is connected across phase to
[360]
neutral is designed for 250 volts but, now it may have to face 433 volts.
[368]
Definitely this high voltage will damage the device.
[371]
Not only this, but floating neutral can also create hazardous touch voltage at equipment’s
[376]
body.
[377]
Because the neutral is broken, electricity will try to flow through different paths.
[381]
It can be equipment’s body also.
[384]
And if someone touches that, that person will have a serious injury or in worst case death.
[391]
If your house has floating neutral, you may experience flickering of lights.
[395]
In such case, you have to immediately call your electrician and get it checked.
[399]
Otherwise you are under very high risk of getting electric shock or fire hazard.
[404]
There are multiple reasons which can cause floating neutral.
[407]
Like
[408]
Neutral broken at source side I.e. at distribution transformer
[412]
If this happens, majority of the customer will face voltage variation.
[416]
Some of them may face very high voltage maximum upto line to line voltage, and some may experience
[423]
low voltage.
[425]
Majority of the equipment connected may get damaged.
[428]
Floating neutral can also happen if the overhead neutral line is broken.
[432]
In such case, customers connected to that phase will be affected.
[437]
It can also happen because of poor workmanship or loose connection.
[441]
If you know any other reason that can lead to floating neutral, do let me know via comments.
[446]
Now, let’s go back to our circuit simulation.
[449]
Where we’ll create floating neutral.
[453]
Here load is unbalanced.
[455]
Neutral is carrying some current.
[457]
Now let’s say the neutral is broken.
[459]
I’ll delete the neutral from load.
[461]
When I delete the neutral see what happens.
[465]
As you see from the reading of voltmeter.
[467]
Voltage across the load in no more constant.
[471]
LED one is having 284 volts, lED two having 168 volts & LED three having 318 volts.
[478]
And our LEDs are meant to handle only 250 volts.
[481]
Now, if the load changes.
[484]
Let me make LED three of 10 watts…..
[491]
As you can see, again the voltage across the load is changed.
[496]
This will keep on changing or keep on floating with the change in the load.
[501]
This situation is what we call as Floating neutral